level meter/Radar water level gauge(10m)
level meter/Radar water level gauge(10m)
level meter/Radar water level gauge(10m)
level meter/Radar water level gauge(10m)
level meter/Radar water level gauge(10m)
level meter/Radar water level gauge(10m)
level meter/Radar water level gauge(10m)
level meter/Radar water level gauge(10m)
level meter/Radar water level gauge(10m)
level meter/Radar water level gauge(10m)

level meter/Radar water level gauge(10m)

$200.00
Color:silvery white
Weight:1kg
measure distance:0~10m
voltage:12V
Quantity
Click to Buy
Click to consult
Detail

Level Meter Technical Specification Document

Radar level meters are widely used in water conservancy projects (reservoir and river level monitoring), municipal sewage treatment, industrial liquid storage tank level control, and environmental hydrological monitoring.

1. Technical Parameters

Parameter

Description

Supply Voltage

DC 7~28V

Current (12V Power Supply)

60mA

Operating Temperature

-40~85°C

Waterproof Rating

IP68

Transmission Frequency

60GHz

Communication Interface

RS-485

Communication Protocol

MODBUS-RTU

Ranging Range

10m

Measurement Accuracy

±3mm

Resolution

1mm

Measurement Time

1s

Start-up Time

<3s

2. Connector Definition

Pin No.

Color

Definition

1

Red

Power Positive

2

Blue

Power Ground

3

Brown

RS485_A(+)

4

Yellow

RS485_B(-)

3. Installation Instructions

When installing the level meter, the beam of the level meter must be perpendicular to the measured surface, and the surface to be measured should be as flat as possible. The radiation angle of the level meter is 12 degrees, and it measures a surface rather than a single point. The readback data is the distance of the surface with the largest reflection area. If there are steps on the test surface, it may easily cause errors in the measured data.

4. 485 Communication Protocol

• Baud Rate: 9600/115200, 8 data bits, no parity bit, 1 stop bit (8, N, 1)

• Note: The upper computer serial port number ranges from 1 to 20 to facilitate communication with USB-to-serial cables extended by USB-HUB.

• RS485 Features: Half-duplex communication, supporting one master and multiple slaves; two-wire system, differential signal, twisted pair.

• Data Rules: The high bit of the data area comes first.

• CRC Check Rule: When the CRC result is placed in the information frame, the low bit comes first.

Example of Communication

• Send: 01 (Address) 03 (Function Code) 00 01 (Starting Register Address: 01) 00 01 (Read 1 Data) D5 CA (CRC Check)

• Receive: 01 (Address) 03 (Function Code) 02 (Number of Bytes Read) 00 01 (Empty Height: 1mm) XX XX (CRC Check)

5. Quick Operation Commands

Function

Command

Response

Parameter Description

Empty Height (cm)

01 03 00 00 00 01 84 0A

01 03 02 00 01 79 84

The returned result is 2 bytes. 0x0001 is in hexadecimal, which converts to 1 in decimal, indicating 1 centimeter.

Empty Height (mm)

01 03 00 01 00 01 D5 CA

01 03 02 00 02 39 85

The returned result is 2 bytes. 0x0002 is in hexadecimal, which converts to 2 in decimal, indicating 2 millimeters.

6. MODBUS Protocol - Read-Only Registers

No.

Register Address

Function

Unit

Remarks

1

00H

Empty Height

cm


2

01H

Empty Height

mm


3

02H

Water Depth

cm

Default: 20 meters minus empty height; total height can be set.

4

03H

Water Depth

mm

Default: 20 meters minus empty height; total height can be set.

5

04H

Address


Default: 0X01

6

05H

Reserved



7

06H

Start Distance

cm


8

07H

End Distance

cm


9

08H

Low Power Consumption Setting


0x001: Low power consumption;<br>0x002: Non-low power consumption

10

09H

Baud Rate


0x001: 9600;<br>0x002: 115200

11

0AH

Reserved


Returns 0X0

12

0BH

Calibration

mm

0x0000 means 0;<br>For negative values: 32768 + absolute value of the negative number;<br>For positive values: Set directly.

13

0CH

Reserved


Returns 0


Radar level gauges useFrequency Modulated Continuous Wave (FMCW) millimeter - wave radar technology, which accurately calculates the level height by transmitting high - frequency electromagnetic waves and receiving reflected signals. Its core advantage lies inNon - contact measurement, which can penetrate complex environments such as steam, foam, and dust without direct contact with the medium, enabling continuous monitoring of media such as liquids, particles, and slurries. The product covers a measuring range of 0 - 20 meters with an accuracy of ±3mm, making it the preferred solution for level measurement in industries such as chemical, power, water treatment, and metallurgy.

Features:

  • Full - scenario coverage: Supports special - shaped containers such as spherical tanks, horizontal tanks, and cylindrical cone tanks, as well as open environments such as open ponds and pumping stations.

  • Strong anti - interference ability: Intelligently suppresses false echoes and operates stably under working conditions such as stirring, fluctuations, and steam.

  • Intelligent interconnection: Supports 4 - 20mA/HART/RS485/Modbus protocols and is compatible with remote debugging and cloud management.