Level Meter Technical Specification Document
1. Technical Parameters
Parameter | Description |
Supply Voltage | DC 7~28V |
Current (12V Power Supply) | 60mA |
Operating Temperature | -40~85°C |
Waterproof Rating | IP68 |
Transmission Frequency | 60GHz |
Communication Interface | RS-485 |
Communication Protocol | MODBUS-RTU |
Ranging Range | 10m |
Measurement Accuracy | ±3mm |
Resolution | 1mm |
Measurement Time | 1s |
Start-up Time | <3s |
2. Connector Definition
Pin No. | Color | Definition |
1 | Red | Power Positive |
2 | Blue | Power Ground |
3 | Brown | RS485_A(+) |
4 | Yellow | RS485_B(-) |
3. Installation Instructions
When installing the level meter, the beam of the level meter must be perpendicular to the measured surface, and the surface to be measured should be as flat as possible. The radiation angle of the level meter is 12 degrees, and it measures a surface rather than a single point. The readback data is the distance of the surface with the largest reflection area. If there are steps on the test surface, it may easily cause errors in the measured data.

4. 485 Communication Protocol
• Baud Rate: 9600/115200, 8 data bits, no parity bit, 1 stop bit (8, N, 1)
• Note: The upper computer serial port number ranges from 1 to 20 to facilitate communication with USB-to-serial cables extended by USB-HUB.
• RS485 Features: Half-duplex communication, supporting one master and multiple slaves; two-wire system, differential signal, twisted pair.
• Data Rules: The high bit of the data area comes first.
• CRC Check Rule: When the CRC result is placed in the information frame, the low bit comes first.
Example of Communication
• Send: 01 (Address) 03 (Function Code) 00 01 (Starting Register Address: 01) 00 01 (Read 1 Data) D5 CA (CRC Check)
• Receive: 01 (Address) 03 (Function Code) 02 (Number of Bytes Read) 00 01 (Empty Height: 1mm) XX XX (CRC Check)
5. Quick Operation Commands
Function | Command | Response | Parameter Description |
Empty Height (cm) | 01 03 00 00 00 01 84 0A | 01 03 02 00 01 79 84 | The returned result is 2 bytes. 0x0001 is in hexadecimal, which converts to 1 in decimal, indicating 1 centimeter. |
Empty Height (mm) | 01 03 00 01 00 01 D5 CA | 01 03 02 00 02 39 85 | The returned result is 2 bytes. 0x0002 is in hexadecimal, which converts to 2 in decimal, indicating 2 millimeters. |
6. MODBUS Protocol - Read-Only Registers
No. | Register Address | Function | Unit | Remarks |
1 | 00H | Empty Height | cm | |
2 | 01H | Empty Height | mm | |
3 | 02H | Water Depth | cm | Default: 20 meters minus empty height; total height can be set. |
4 | 03H | Water Depth | mm | Default: 20 meters minus empty height; total height can be set. |
5 | 04H | Address | Default: 0X01 | |
6 | 05H | Reserved | ||
7 | 06H | Start Distance | cm | |
8 | 07H | End Distance | cm | |
9 | 08H | Low Power Consumption Setting | 0x001: Low power consumption;<br>0x002: Non-low power consumption | |
10 | 09H | Baud Rate | 0x001: 9600;<br>0x002: 115200 | |
11 | 0AH | Reserved | Returns 0X0 | |
12 | 0BH | Calibration | mm | 0x0000 means 0;<br>For negative values: 32768 + absolute value of the negative number;<br>For positive values: Set directly. |
13 | 0CH | Reserved | Returns 0 |
Radar level gauges useFrequency Modulated Continuous Wave (FMCW) millimeter - wave radar technology, which accurately calculates the level height by transmitting high - frequency electromagnetic waves and receiving reflected signals. Its core advantage lies inNon - contact measurement, which can penetrate complex environments such as steam, foam, and dust without direct contact with the medium, enabling continuous monitoring of media such as liquids, particles, and slurries. The product covers a measuring range of 0 - 20 meters with an accuracy of ±3mm, making it the preferred solution for level measurement in industries such as chemical, power, water treatment, and metallurgy.
Full - scenario coverage: Supports special - shaped containers such as spherical tanks, horizontal tanks, and cylindrical cone tanks, as well as open environments such as open ponds and pumping stations.
Strong anti - interference ability: Intelligently suppresses false echoes and operates stably under working conditions such as stirring, fluctuations, and steam.
Intelligent interconnection: Supports 4 - 20mA/HART/RS485/Modbus protocols and is compatible with remote debugging and cloud management.