Radar level meters are widely used in water conservancy projects (reservoir and river level monitoring), municipal sewage treatment, industrial liquid storage tank level control, and environmental hydrological monitoring. With the characteristics of resistance to rain, fog, high and low temperatures, they can operate stably in complex and harsh environments, realizing accurate and real-time level data collection and transmission.
1. Operating Parameters
Parameter | Description |
Supply Voltage | DC 7~28V |
Current (12V Power Supply) | Average current is about 60mA (5—100mA) during normal operation |
Operating Temperature | -40~85°C |
Waterproof Rating | IP68 |
Transmission Frequency | 24~25.8GHz |
Communication Interface | RS-485 |
Communication Protocol | MODBUS-RTU |
1.2 Measurement Parameters
Parameter | Description |
Ranging Range | 40m |
Measurement Accuracy | ±3mm |
Resolution | 3mm |
Measurement Time | 1s |
Start-up Time | <3s |
1.3 Wiring
The cable description shall be corresponding to the actual goods:
Four-core Cable:
Pin No. | Color | Definition |
1 | Red | Power Positive |
2 | Blue | Power Ground |
3 | Brown | RS485_A(+) |
4 | Yellow | RS485_B(-) |
1.4 Communication Interface
1.4.1 RS485 Interface
The green cable is RS485A(+), and the yellow cable is RS485B(-). When communicating with RS485 interface, the basic settings are as follows:
Baud Rate | 9600 (default) |
Parity Bit | None |
Data Bits | 8 |
Stop Bits | 1 |
2. 485 Communication Protocol
2.1 Detailed Protocol Specifications
2.1.1 Basic Communication Settings
9600/115200, 8, N, 1; (The upper computer serial port number ranges from 1 to 20 to facilitate communication with USB-to-serial cables extended by USB-HUB). RS485; (Half-duplex communication, supporting one master and multiple slaves; two-wire system, differential, twisted pair; *Data Rules: The high bit of the data area comes first; *CRC Check Rule: When the CRC result is placed in the information frame, the low bit comes first).
2.1.2 Communication Example
Address Field: The valid address range of the slave (target address) is 1~247, supporting broadcast send-receive address 0xFF and broadcast receive-only address 0xFE. When using the broadcast address, ensure that only one sensor is connected; otherwise, it will cause data errors or hardware damage.
Function Field: Valid codes are 1~255. The ultrasonic flow meter supports 0x03, 0x06, and 0x10 function codes.
Data Field: The data field consists of multiple groups of such data—two hexadecimal numbers as a group, ranging from 00~FF.
CRC Check Code: After CRC generation, the low byte comes first and the high byte comes after.
T1, T2, T3, T4 represent the transmission time length of each byte, totaling four byte transmission delay times.
9600, 8, N, 1; (The upper computer serial port number ranges from 1 to 20 to facilitate communication with USB-to-serial cables extended by USB-HUB).
RS485; (Half-duplex communication, supporting one master and multiple slaves; two-wire system, differential, twisted pair;
Data Rules: The high bit of the data area comes first;
CRC Check Rule: When the CRC result is placed in the information frame, the low bit comes first.
2.1.2 Ultrasonic Flow Meter Register Variable Status Table
U16: Unsigned 16-bit integer
No. | Register Address | Function | Unit | Remarks |
1 | 00H | Device Temperature, signed number, scale factor +100 | 0.01°C | Invalid |
2 | 01H | Instantaneous Velocity | mm/s | For testing |
3 | 02H | Average Velocity | mm/s | Customers should use this result |
4 | 03H | Reserved | ||
5 | 04H | Flow Direction | 1: Downstream | |
6 | 05H | Installation Angle, scale factor +100 | 0.01° | Angle with horizontal plane |
7 | 06H | Device Voltage | mV | Device Voltage |
8 | 07H | Jump Filter Status | 1: Jump | |
9 | 08H | Instantaneous Flow Rate (m³/S) | Independent flow register, exists independently of the previous registers and is discontinuous | |
10 | 09H | Water Depth | cm | |
11 | 0AH | Midline Velocity | mm/S | |
12 | 0BH | Low Power Consumption Setting | 0x001: Low power consumption; | |
13 | 0CH | Baud Rate | 0x001: 9600; | |
14 | 0DH | Gain Value | 0x0000: Auto gain; others are set gain values | |
15 | 0EH | Time Domain Threshold | ||
16 | 0FH | Frequency Domain Threshold | ||
17 | A0H | Address |